Hitachi SJ Series P1 VFDs
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.
Overview
Variable frequency drive (VFD) series made by Hitachi. Useful for powering spindles of CNC routers.
Factory reset
To perform a factory reset of the VFD, set the following parameters in this order:
- set Ub-01 to 04
- set Ub-02 to 02
- set Ub-05 to 01
- (wait for initialization to complete)
Modbus control
VFD parameters
Name | Value | Default | Description |
---|---|---|---|
AA101 | 08: RS-485 | 01: Ai1 terminal | speed command source |
AA111 | 03: RS-485 | 00: FW/RV terminals | operation command source |
CF-01 | 05: 9600 baud | 05: 9600 baud | RS-485 baud |
CF-02 | 1 | 1 | Modbus slave address |
CF-03 | 00: no parity | 00: no parity | RS-485 parity |
CF-04 | 1 | 1 | RS-485 stop bits |
CF-05 | 04: deceleration stop | 02: ignore | RS-485 communication error handling |
CF-06 | 2.00 seconds | 0.00 seconds | RS-485 communication timeout time |
CF-07 | 2ms | 0ms | RS-485 communication waiting time |
CF-08 | 01:Modbus-RTU | 01:Modbus-RTU | communication method |
Modbus coils/registers
TODO
mbpoll
# turn on output ./mbpoll /dev/ttyUSB0 1 -b 9600 -s 1 -P none -a 1 -r 1 -t 0 -B # turn off output ./mbpoll /dev/ttyUSB0 0 -b 9600 -s 1 -P none -a 1 -r 1 -t 0 -B # write 60Hz output frequency as Hz * 100 (2-place fixed point in decimal) ./mbpoll /dev/ttyUSB0 6000 -b 9600 -s 1 -P none -a 1 -r 10502 -t 4:int -B
Online Resources
Inverter : SJ series P1 : Hitachi Industrial Equipment Systems
Hitachi SJ Series P1 Basic Guide