Difference between revisions of "AutomationDirect DURApulse GS20 Series VFDs"

From CNC Wiki
Jump to navigation Jump to search
(updated software links)
(added parameter, error code, and Modbus information)
 
(2 intermediate revisions by the same user not shown)
Line 44: Line 44:
 
| 245,048,446 bytes
 
| 245,048,446 bytes
 
| f274adb0afc390d777bdcfc624b7e17a
 
| f274adb0afc390d777bdcfc624b7e17a
| SHA1
+
| 02c591e95576d2e8180062f4f8b04d36ec478046
 
|}
 
|}
  
Line 60: Line 60:
 
| c43013f34c64291d8c4b2ebfa4cbab2a1f68ff27
 
| c43013f34c64291d8c4b2ebfa4cbab2a1f68ff27
 
|}
 
|}
 +
 +
== Parameters ==
 +
 +
* [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=89 Page 89] (4-3 in the PDF) has the parameter table
 +
* [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=136 Page 139] (4-50 in the PDF) gives detailed descriptions of the parameters
 +
 +
== Alarm Codes ==
 +
 +
* [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=384 Page 384] (6-8 in the PDF) list the warning codes
 +
* [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=401 Page 401] (6-25 in the PDF) list the fault codes
 +
 +
== Modbus control ==
 +
 +
* [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=359 Page 359] (5-1 in the PDF) is the chapter on "Serial Communications"
 +
 +
=== VFD parameters ===
 +
 +
{| class="wikitable"
 +
! Modbus Address
 +
! Parameter No.
 +
! Default Value
 +
! Required Value
 +
! Description
 +
|-
 +
| 0x0014
 +
| P00.20
 +
| 0: digital keypad
 +
| 1: RS-485 communication input
 +
| Master frequency command source
 +
|-
 +
| 0x0015
 +
| P00.21
 +
| 0: digital keypad
 +
| 2: RS-485 communication input
 +
| Operation command source
 +
|-
 +
| 0x0900
 +
| P09.00
 +
| 1
 +
| 1
 +
| Slave Address
 +
|-
 +
| 0x0901
 +
| P09.01
 +
| 9.6
 +
| 9.6
 +
| Baudrate
 +
|-
 +
| 0x0902
 +
| P09.02
 +
| 3: no warning, no fault, and continue operation
 +
| 2: fault and coast to stop
 +
| Communication Fault Handling
 +
|-
 +
| 0x0903
 +
| P09.03
 +
| 0.0
 +
| 2.0
 +
| Timeout Detection
 +
|-
 +
| 0x0904
 +
| P09.04
 +
| 15: 8, O, 1 (RTU)
 +
| 15: 8, O, 1 (RTU)
 +
| Communication Protocol
 +
|-
 +
| 0x0909
 +
| P09.09
 +
| 2.0
 +
| 2.0
 +
| Communication Response Delay
 +
|}
 +
 +
From [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=360 Page 360] (5-2 in the PDF)
 +
 +
=== Modbus registers ===
 +
 +
* [https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf#page=364 Page 364] (5-6 in the PDF) lists the status registers
  
 
== Bill of Materials ==
 
== Bill of Materials ==
Line 76: Line 154:
  
 
[https://www.automationdirect.com/drives/ac-drives/gs20 AC Drives GS20 and GS20X | AutomationDirect]
 
[https://www.automationdirect.com/drives/ac-drives/gs20 AC Drives GS20 and GS20X | AutomationDirect]
 +
 +
[https://www.automationdirect.com/adc/shopping/catalog/drives_-a-_soft_starters/ac_variable_frequency_drives_(vfd)/general_purpose_vfds/gs23-45p0#docsanchor AutomationDirect DURApulse GS23-45P0 Downloads]
  
 
[https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf AutomationDirect DURApulse GS20 & GS20X Drive User Manual (GS20_UMW, 1st Edition, Rev D)]
 
[https://cdn.automationdirect.com/static/manuals/gs20m/gs20m.pdf AutomationDirect DURApulse GS20 & GS20X Drive User Manual (GS20_UMW, 1st Edition, Rev D)]

Latest revision as of 08:22, 4 March 2024

DURApulse GS21-11P0 stock photo

Overview

Taiwanese variable frequency drives (VFDs). They feature Modbus/RS-485 support.

Model Numbers

  • Page 38 (1-30 in the PDF) shows the model number scheme

Wiring Diagram

  • Page 62 (2-24 in the PDF) shows the power terminals pinout
  • Page 66 (2-28 in the PDF) shows the power terminals layout
  • Page 69 (2-31 in the PDF) shows the power terminals wiring diagram
  • Page 69 (2-31 in the PDF) shows the control terminals pinout
  • Page 72 (2-34 in the PDF) shows the control terminals layout
  • Page 74 (2-36 in the PDF) shows the control terminals wiring diagram
  • Page 76 (2-38 in the PDF) shows the full wiring diagram
  • Page 368 (5-11 in the PDF) shows the RJ45 Modbus/RS-485 pinout

Dimensions

  • Page 44 (2-6 in the PDF) shows the dimensions

Software

Software & Firmware Downloads

GSOFT2 Drive Configuration Software

Filename Size MD5 SHA1
GSoft2_V2.0.2.1.zip 252,209,721 bytes 60aea9a1eac3ab52112fdaddcf61ea70 ac34673e94a6175bce5b0fa30ba203aeda8e638b
gsoft2_v2.0.0.7.zip 245,048,446 bytes f274adb0afc390d777bdcfc624b7e17a 02c591e95576d2e8180062f4f8b04d36ec478046

GSLogic Drive PLC Software

Filename Size MD5 SHA1
gslogic_v1.02.zip 28,959,436 bytes 4f1ad6c07ecc4a88ca77ea89558caa29 c43013f34c64291d8c4b2ebfa4cbab2a1f68ff27

Parameters

  • Page 89 (4-3 in the PDF) has the parameter table
  • Page 139 (4-50 in the PDF) gives detailed descriptions of the parameters

Alarm Codes

  • Page 384 (6-8 in the PDF) list the warning codes
  • Page 401 (6-25 in the PDF) list the fault codes

Modbus control

  • Page 359 (5-1 in the PDF) is the chapter on "Serial Communications"

VFD parameters

Modbus Address Parameter No. Default Value Required Value Description
0x0014 P00.20 0: digital keypad 1: RS-485 communication input Master frequency command source
0x0015 P00.21 0: digital keypad 2: RS-485 communication input Operation command source
0x0900 P09.00 1 1 Slave Address
0x0901 P09.01 9.6 9.6 Baudrate
0x0902 P09.02 3: no warning, no fault, and continue operation 2: fault and coast to stop Communication Fault Handling
0x0903 P09.03 0.0 2.0 Timeout Detection
0x0904 P09.04 15: 8, O, 1 (RTU) 15: 8, O, 1 (RTU) Communication Protocol
0x0909 P09.09 2.0 2.0 Communication Response Delay

From Page 360 (5-2 in the PDF)

Modbus registers

  • Page 364 (5-6 in the PDF) lists the status registers

Bill of Materials

The microcontroller is marked:

5F562TABDFP
1933
T?H303?60

Renesas R5F562TABDFP#11 | DigiKey

Renesas R5F562TABDFP#V3 | Mouser

Online Resources

AC Drives GS20 and GS20X | AutomationDirect

AutomationDirect DURApulse GS23-45P0 Downloads

AutomationDirect DURApulse GS20 & GS20X Drive User Manual (GS20_UMW, 1st Edition, Rev D)