ABB ACS550 VFD: Difference between revisions

added website link for VFD
added mbpoll commands
Line 12: Line 12:


[https://library.e.abb.com/public/0437a01ff99446478a7656edf836e25c/DWL_2_95_update.exe DriveWindow Light 2.95 (update?) installer]
[https://library.e.abb.com/public/0437a01ff99446478a7656edf836e25c/DWL_2_95_update.exe DriveWindow Light 2.95 (update?) installer]
== Modbus Control ==
=== mbpoll ===
There is an open source utility that can speak Modbus over a serial port (or USB to serial) that has an RS-485 adapter attached. It's called mbpoll:
https://github.com/epsilonrt/mbpoll
<code>mbpoll</code> commands to interact with the VFD:
<pre># monitor output frequency (displays Hz * 10)
./mbpoll /dev/ttyUSB0 -b 9600 -s 1 -P none -a 1 -r 103 -t 4
# monitor output current (displays A * 10)
./mbpoll /dev/ttyUSB0 -b 9600 -s 1 -P none -a 1 -r 104 -t 4
# monitor output power (displays kW * 10)
./mbpoll /dev/ttyUSB0 -b 9600 -s 1 -P none -a 1 -r 106 -t 4
# monitor output voltage (displays V)
./mbpoll /dev/ttyUSB0 -b 9600 -s 1 -P none -a 1 -r 109 -t 4</pre>