Folinn H1 Series VFDs: Difference between revisions

added LinsVFD EV50 series manual page links
added more parameters to enable MODBUS timeout fault
 
(2 intermediate revisions by the same user not shown)
Line 36: Line 36:
* [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=76 Page 76] (147 in the PDF) shows the H0201 interface panel screw / RJ45 / D-Sub? terminal pinout
* [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=76 Page 76] (147 in the PDF) shows the H0201 interface panel screw / RJ45 / D-Sub? terminal pinout


NOTE: they claim that pins 1&2 on the RJ45 are RS-485+/-, but in reality it's reversed and pins 8&7 are RS-485+/- and pins 2&4 are GND.
NOTE: <del>they claim that pins 1 &amp; 2 on the RJ45 are RS-485+/-</del>, but in reality it's reversed and pins 8 &amp; 7 are RS-485+/- and pins 1 &amp; 2 are +5V &amp; GND respectively.
 
=== RS-485 ===
 
{| class="wikitable"
! RJ45 Pin
! Function
|-
| 1
| +5V
|-
| 2
| GND
|-
| 3
| +12V
|-
| 7
| RS-485 B-
|-
| 8
| RS-485 A+
|}


== Dimensions ==
== Dimensions ==
Line 285: Line 307:
| 2: communication (?)
| 2: communication (?)
| Pause command source
| Pause command source
|}
To configure MODBUS timeout:
{| class="wikitable"
! Parameter No.
! Default Value
! Required Value
! Description
|-
| P01.30
| 0000
| 1340: Comparator 1 Output
| Virtual terminal setting
|-
| P03.08
| 00: no effect
| 17: use P01.30 bit 0 (in single command mode)
| Fault command source
|-
| P12.00
| 0.0
| 2.0 (seconds until timeout)
| Free parameter 1
|-
| P16.00
| 0000: invalid?
| 1044: use P10.44 "communication timeout"
| Comparator 1 input parameter selection
|-
| P16.01
| 0000: invalid
| 1200: use P12.00 "free parameter 1"
| Comparator 1 comparison parameter selection
|-
| P16.02
| 0: &gt; (greater than)
| 2: &ge; (greater than or equal to)
| Comparator 1 configuration
|}
|}