AutomationDirect GS2 Series VFDs: Difference between revisions
added Modbus register tables |
added corrected RS-485 pinout |
||
| Line 12: | Line 12: | ||
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=26 Page 26] (2-10 in the PDF) shows the control terminal layout | * [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=26 Page 26] (2-10 in the PDF) shows the control terminal layout | ||
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=27 Page 27] (2-11 in the PDF) shows an overview of the wiring | * [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=27 Page 27] (2-11 in the PDF) shows an overview of the wiring | ||
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=134 Page 134] (5-30 in the PDF) shows the RS-232/RS-485 wiring | |||
NOTE: the manual lists the RS-485 wiring SG+ and SG- swapped! SG+ is really B- and SG- is really A+, this is the correct RJ12 (6P4C) pinout: | |||
{| class="wikitable" | |||
! RJ12 Pin | |||
! Function | |||
|- | |||
| 2 | |||
| GND | |||
|- | |||
| 3 | |||
| A+ (manual says SG-!) | |||
|- | |||
| 4 | |||
| B- (manual says SG+!) | |||
|- | |||
| 5 | |||
| +5V | |||
|} | |||
== Dimensions == | == Dimensions == | ||