== Model Numbers == | == Model Numbers == | ||
In the FoLinn H1 series manual: | |||
* [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=6 Page 6] (7 in the PDF) shows the model number scheme | * [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=6 Page 6] (7 in the PDF) shows the model number scheme | ||
In the LinsVFD EV50 series manual: | |||
* [https://www.omc-stepperonline.com/index.php?route=product/product/get_file&file=3332/EV50_Series_Inverter_Full_User_Manual.pdf#page=6 Page 6] (7 in the PDF) shows the model number scheme | |||
== Wiring Diagram == | == Wiring Diagram == | ||
| Line 30: | Line 36: | ||
* [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=76 Page 76] (147 in the PDF) shows the H0201 interface panel screw / RJ45 / D-Sub? terminal pinout | * [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=76 Page 76] (147 in the PDF) shows the H0201 interface panel screw / RJ45 / D-Sub? terminal pinout | ||
NOTE: they claim that pins 1&2 on the RJ45 are RS-485+/-, but in reality it's reversed and pins 8&7 are RS-485+/- and pins 2& | NOTE: <del>they claim that pins 1 & 2 on the RJ45 are RS-485+/-</del>, but in reality it's reversed and pins 8 & 7 are RS-485+/- and pins 1 & 2 are +5V & GND respectively. | ||
=== RS-485 === | |||
{| class="wikitable" | |||
! RJ45 Pin | |||
! Function | |||
|- | |||
| 1 | |||
| +5V | |||
|- | |||
| 2 | |||
| GND | |||
|- | |||
| 3 | |||
| +12V | |||
|- | |||
| 7 | |||
| RS-485 B- | |||
|- | |||
| 8 | |||
| RS-485 A+ | |||
|} | |||
== Dimensions == | == Dimensions == | ||
In the FoLinn H1 series manual: | |||
* [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=65 Page 65] (126 in the PDF) show a table of the dimensions | * [https://www.cncwiki.org/images/c/c1/FoLinn_H1_Series_Inverter_User_Manual.pdf#page=65 Page 65] (126 in the PDF) show a table of the dimensions | ||
In the LinsVFD EV50 series manual: | |||
* [https://www.omc-stepperonline.com/index.php?route=product/product/get_file&file=3332/EV50_Series_Inverter_Full_User_Manual.pdf#page=65 Page 65] (126 in the PDF) show a table of the dimensions | |||
== Parameters == | == Parameters == | ||
| Line 273: | Line 307: | ||
| 2: communication (?) | | 2: communication (?) | ||
| Pause command source | | Pause command source | ||
|} | |||
To configure MODBUS timeout: | |||
{| class="wikitable" | |||
! Parameter No. | |||
! Default Value | |||
! Required Value | |||
! Description | |||
|- | |||
| P01.30 | |||
| 0000 | |||
| 1340: Comparator 1 Output | |||
| Virtual terminal setting | |||
|- | |||
| P03.08 | |||
| 00: no effect | |||
| 17: use P01.30 bit 0 (in single command mode) | |||
| Fault command source | |||
|- | |||
| P12.00 | |||
| 0.0 | |||
| 2.0 (seconds until timeout) | |||
| Free parameter 1 | |||
|- | |||
| P16.00 | |||
| 0000: invalid? | |||
| 1044: use P10.44 "communication timeout" | |||
| Comparator 1 input parameter selection | |||
|- | |||
| P16.01 | |||
| 0000: invalid | |||
| 1200: use P12.00 "free parameter 1" | |||
| Comparator 1 comparison parameter selection | |||
|- | |||
| P16.02 | |||
| 0: > (greater than) | |||
| 2: ≥ (greater than or equal to) | |||
| Comparator 1 configuration | |||
|} | |} | ||