Line 108: Line 108:
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=108 Page 108] (5-4 in the PDF) lists the parameter registers
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=108 Page 108] (5-4 in the PDF) lists the parameter registers
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=113 Page 113] (5-9 in the PDF) lists the status registers
* [https://cdn.automationdirect.com/static/manuals/gs2m/gs2m.pdf#page=113 Page 113] (5-9 in the PDF) lists the status registers
Command registers:
{| class="wikitable"
! Parameter No.
! Register No. (hex)
! Register No. (decimal)
! Values
! Description
|-
| P09.26
| 0x091A
| 2330
| 0 - 4000 (Hz * 10)
| Serial Comm Speed Reference
|-
| P09.27
| 0x091B
| 2331
| 00: Stop<br/>01: Run
| Serial Comm RUN Command
|-
| P09.28
| 0x091C
| 2332
| 00: Forward<br/>01: Reverse
| Serial Comm Direction Command
|-
| P09.29
| 0x091D
| 2333
| 00: No fault<br/>01: External fault
| Serial Comm External Fault
|-
| P09.30
| 0x091E
| 2334
| 00: No action<br/>01: Fault reset
| Serial Comm Fault Reset
|-
| P09.31
| 0x091F
| 2335
| 00: Stop<br/>01: Jog
| Serial Comm JOG Command
|}
Status registers:
{| class="wikitable"
! Register No. (hex)
! Register No. (decimal)
! Description
|-
| 0x2100
| 8448
| Status Monitor 1
|-
| 0x2101
| 8449
| Status Monitor 2
|-
| 0x2102
| 8450
| Frequency Command F
|-
| 0x2103
| 8451
| Output Frequency H
|-
| 0x2104
| 8452
| Output Current A
|-
| 0x2105
| 8453
| DC Bus Voltage d
|-
| 0x2106
| 8454
| Output Voltage U
|-
| 0x2107
| 8455
| Motor RPM
|-
| 0x2108
| 8456
| Scale Frequency (Low Word)
|-
| 0x2109
| 8457
| Scale Frequency (High Word)
|-
| 0x210A
| 8458
| Power Factor Angle
|-
| 0x210B
| 8459
| % Load
|-
| 0x2110
| 8464
| Firmware Version
|}